Chapter 8: Managing External Devices 
 
192
 
 
 
Schroff LHX Heat Exchangers 
After connecting the Schroff
®
 LHX heat exchanger to the EMX device via 
the Feature port or the RS-485 port, the EMX detects LHX. The LHX is 
viewed under the Feature folder or the Auxiliary Port folder in the 
navigation tree, depending on the port it is connected to. 
Note: If connecting the LHX to the Feature port, use the serial cable 
provided with the LHX. 
From the EMX, you can remotely do the following: 
 
Name a connected LHX heat exchanger 
 
Configure the air outlet temperature setpoint  
 
Configure air outlet temperature thresholds 
 
Configure air inlet temperature thresholds 
 
Configure water inlet temperature thresholds 
 
Configure fan speed thresholds 
 
Monitor the air inlet temperature 
 
Monitor the air outlet temperature 
 
Monitor the fan speed 
 
Configure basic settings for the connected heat exchanger, such as 
the sensor thresholds 
Note: These settings are stored on the EMX port where the heat 
exchanger is connected, and are lost if that heat exchanger is moved to 
a different port. 
See 
Connecting a Schroff LHX Heat Exchanger (Optional)
 (on page 
41) for how to connect the heat exchanger. 
 
Enabling and Disabling Schroff LHX Heat Exchanger Support 
By default, Schroff LHX Heat Exchanger support is disabled. As such, 
support needs to be enabled before the device appears in the navigation 
tree or on the dashboard. Additionally, Schroff LHX Heat Exchanger 
support must be enabled in order for the LHX-MIB to be accessible 
through SNMP. 
 
To enable the Schroff LHX Heat Exchanger: 
1.  Select Device Settings > Features, and then select the Schroff Heat 
Exchanger checkbox on the menu. 
2.  Click Yes to confirm. 
3.  Reboot the EMX.