Altitude Correction Factors (EMX) 
If a Raritan differential air pressure sensor is attached to your device, the 
altitude you enter for the device can serve as an altitude correction 
factor. That is, the reading of the differential air pressure sensor will be 
multiplied by the correction factor to get a correct reading. 
This table shows the relationship between different altitudes and 
correction factors. 
Altitude (meters) 
Altitude (feet) 
Correction factor 
0.95 
250 
820 
0.98 
425 
1394 
1.00 
500 
1640 
1.01 
740 
2428 
1.04 
1500 
4921 
1.15 
2250 
7382 
1.26 
3000 
9842 
1.38 
 
 
Maximum Ambient Operating Temperature (EMX) 
The maximum ambient operating temperature (TMA) for the EMX is the 
same for all models regardless of the certification standard (CE or UL). 
Specification 
Measure 
Max Ambient Temperature 
60 degrees Celsius 
 
 