Honeywell HC900 Manual Do Utilizador

Página de 228
Diagnostics and Troubleshooting - User Interface 
Revision 5 
  HC900 Hybrid Controller Installation and User Guide 
137 
9/03  
Table 30 - Scanner Diagnostics 
Diagnostic 
Condition 
Number 
of 
Strobes  
Possible Cause 
Scanner Action User 
Action 
Watchdog Reset 
Watchdog reset resulting from 
software failure 
Scanner restarts and 
requests configuration 
from the main CPU. 
1. Cycle power to the scanner 
2. Upgrade scanner software 
3. Replace scanner module 
4. Contact Honeywell Personnel.
 
Prefetch abort 
CPU exception 
CPU failed when attempting to 
fetch an instruction from the 
prefetch register. 
See watchdog reset 
1. Cycle power to the scanner 
2. Isolate system from noise and 
cycle power to the scanner 
3. Replace scanner module
 
Address error 
CPU exception 
The reserved exception 
occurred for an unknown 
reason. 
See watchdog reset 
See Prefetch abort CPU 
exception 
Undefine 
instruction CPU 
exception 
Bad Instruction Detected 
See watchdog reset 
See Prefetch abort CPU 
exception 
Data abort CPU 
exception 
CPU failed when attempting to 
access data. 
See watchdog reset 
See Prefetch abort CPU 
exception 
Software interrupt 
exception 
Spurious Interrupt 
See watchdog reset 
See Prefetch abort CPU 
exception 
Vector error 
Interrupt vectors in RAM were 
corrupted 
Interrupt vectors were 
restored 
See Watchdog reset 
Flash write error 
Flash failed to burn properly. 
The boot code is the 
only software running. 
This software waits 
for a request to burn 
the flash. It does no 
scanning of modules. 
Modules remain in 
their failsafe state.  
Do a code download. 
Rack backplane 
failure 
The Scanner is unable to 
successfully communicate to 
any modules that are in its SPI 
backplane. 
Does no scanning of 
modules. Modules 
remain in their failsafe 
state. 
1. Remove modules and check 
for bent pins on connectors. 
2. Reinsert modules one at a time 
and note which module the 
diagnostic reoccurs, and 
replace that module. 
3. Cycle power to the rack. 
4. Replace the power supply. 
5. Replace the rack. 
6. Replace the scanner module.