Roberts Gorden 200 Manual Do Utilizador

Página de 62
SECTION 10: W
IRING
21 of 51
SECTION 10: WIRING
All heater models require constant 120 V / 1Ø / 60 
Hz power supply. Check heater rating plate for 
electrical rating for proper circuit sizing. For 
servicing, a disconnect switch of proper electrical 
rating should be installed in the vicinity of the heater.
All heaters are equipped with thermostat 
connections suitable to power a 24 V thermostat.
Heater must be wired and electrically grounded in 
accordance with local codes. In the absence of local
codes in accordance with: United States: refer to 
National Electrical Code
®
 NFPA 70 - latest revision 
Canada: refer to Canadian Electrical Code CSA 
C22.1 Part I - latest revision. 
10.1 Positioning Thermostats 
A room thermostat should be mounted on a 
vibration-free wall or column at a height of 
approximately 5' (1.5 m) from the floor to measure 
the ambient temperature. It should be clear of both 
cold drafts and the direct path of warm air from the 
heater.
Avoid mounting thermostat on outside walls or in 
areas directly exposed to radiant heat or sunlight.
Install wall tag in a visible location near thermostat.
See Page 5, Section 2.1 for wall tag details.
10.1.1 Fan Control
The heater’s axial fan can be used during the off-
season for air circulation. A low voltage 
programmable thermostat with fan switch (P/N 
90425400) must be used. 
See Page 21, Section 
10.2 for thermostat connection details. For the use 
of multiple heaters on one thermostat, 
See Page 22, 
Section 10.3  through Page 23, Section 10.4.
10.2 Low Voltage Thermostat with One Heater
DANGER
Electrical Shock Hazard
Disconnect electric before service.
More than one disconnect switch may be 
required to disconnect electric from 
equipment.
Equipment must be properly grounded.
Failure to follow these instructions can result 
in death or electrical shock.
R
G
W
C
Electrical 
Supply
Terminal
Strip
R
W
R
G
24 Volt
Thermostat
Heating Only
24 Volt
Thermostat
with Fan Control
W
C
Terminal
Strip
Electrical 
Supply
R
G
W
C
Gas Supply
Gas Supply