Installation
800937
22
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Electrical Plug Connection
Three-Wire Plug
Figure 26 
1. Remove access cover from rear of dryer.
Figure 27 
2. Use a strain relief and insert end of power cord 
through power supply hole.
Figure 28 
D816I
1
3-Wire Grounded Neutral 120/240 Volt, 60 Hertz 
AC 1 Phase Service Entrance Switch Box 
(See NOTE above)
4
Metallic or Non-Metallic Sheathed Cable 
(Copper wire only)
5
Pigtail to Dryer (See NOTE above)
2
30 Ampere Fuses or Circuit Breaker
6
Neutral 
3
Neutral Wire
7
Terminal Block in Dryer
NOTE: The power cord (pigtail) is NOT supplied with the electric 
dryer. Type of pigtail and gauge of wire must conform to local 
codes and instructions.
The method of wiring the dryer is optional and subject to local 
code requirements.
NOTE: Connect the dryer to the power supply with the 
MAXIMUM RATED VOLTAGE listed on the nameplate.
1
2
3
4
5
6
7
POWER SUPPLY
POWER SUPPLY
INTERMEDIATE 
FUSE BOX (May 
be omitted if 
service entrance 
box is fused)
WALL RECEPTACLE
PIGTAIL CONNECTION
L1
L2
L1
L2
DIRECT CONNECTION
INTERMEDIATE
SHUT-OFF BOX
(May or may 
not be fused)
120 ± 12
V.A.C.
A typical 
30-Amp 
Three-wire 
Receptacle 
NEMA Type 
10-30R
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIRE only. 
k
Shorter than 15
k (4.5 m) use 10 A.W.G. 
Longer than 15
k (4.5 m) use 8 A.W.G.
D695I
D696I