Honeywell T8024F Manual Do Utilizador

Página de 8
T8001F, T8024F FLUSH MOUNT PROGRAMMABLE THERMOSTAT
7
69-1465—3
CHECKOUT
Heating
1. Slide the SYSTEM switch to Heat and the FAN 
switch to Auto.
2. Press and hold the ▲ key to raise the temperature 
setting several degrees above the room tempera-
ture; the heating equipment should start. In con-
ventional systems, the system turns on the fan 
through the use of a time delay relay or through a 
limit control. When the fan operation (fuel) switch is 
in the E position, the fan starts immediately.
3. Press the ▼ key to lower the temperature setting 
below the room temperature. Heating equipment 
should stop.
Cooling
CAUTION
Damage To compressor possible.
Operating at too low of an outdoor 
temperature may cause compressor damage.
Do not operate cooling if outdoor temperature is 
below 50°F (10°C). 
Allow compressor to remain off for five minutes 
before restarting.
Refer to manufacturer’s recommendations.
1. Slide the SYSTEM switch to Cool and the FAN 
switch to Auto.
2. Press the ▼ key to lower the temperature setting 
several degrees below the room temperature; the 
cooling equipment should start. The fan starts and 
stops with the cooling equipment.
NOTE: If unit doesn’t start immediately, remem-
ber, the thermostat has a built-in minimum 
off-time of five minutes to protect the com-
pressor.
3. Press the ▲ key to raise the temperature setting 
above the room temperature. Cooling system 
should shut down.
Fan
1. Slide the SYSTEM switch to Off and the FAN 
switch to On. The fan should run continuously.
2. Slide the FAN switch to Auto. In heating, the fan is 
controlled directly by the heating equipment and 
may start a few minutes after the heating equip-
ment turns on (on most systems). In cooling, the 
fan starts and stops with the cooling equipment.
Be sure all equipment responds correctly to the 
thermostat.