Honeywell pro th4110d Manual Do Utilizador

Página de 16
1
0
Installation Guide
8
1
5
9
13
14
15
System type
Heating cycle rate
(CPH: cycles/hour)
Compressor
cycle rate (CPH)
Adaptive Intelligent
Recovery
Temperature 
display
Compressor 
protection
0 Gas, oil or electric heat with air conditioning
1
Heat pump (5 minute compressor off time in heating and cooling)
5 For gas or oil furnaces of less than 90% efficiency
1
For steam or gravity systems
3
For hot water systems & furnaces of over 90% efficiency
9
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
3 Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
1 On 
**See page 10
0
Off
0 Fahrenheit
1
Celsius
5 Five-minute compressor off time 
**See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
Setup Function
Settings & Options
To begin, press and hold the and
buttons until the display changes
Function
number
Press 
to change settings
Press 
to advance to next function
Press and hold
to exit and save settings
Setting
Installer setup
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Setup
Installer system test
After completing the installer setup above, press the 
button again to begin a
system test (see next page).
Press and hold both buttons