Set Up and Calibration Procedures 
Calibration 
66 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Calibration Set up 
 
Follow the steps below to set up the test equipment and actuator to verify calibration or perform calibration 
procedures. 
Step 
Action 
Determine input type (current or voltage). 
Set jumper W2 on main CPU board according to type of signal source.  See Figure 27 on page 
68 for jumper location. 
Connect the copper leads from the signal source to the input terminals of the actuator as 
shown in Figure 25.   
Place signal source output at zero and switch power on.   
Connect a 250 ohm resistor across the Output terminals of the actuator and connect the DVM 
leads to the terminals.   
 
 
 
 
Actuator
Input
5     4
-
+
Output
2    1     
-
+
+
-
Calibrated
Signal
Source
Digital
Voltmeter
+ -
Terminal Block
Internal 250 ohm resistor
settable through 
Jumper W2
Current
Voltage
250 ohm 
resistor 
(supplied)
 
 
 
Figure 25 Calibration Wiring Connections (non-slidewire emulation)