Set Up and Calibration Procedures
Calibration
Revision 7
HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual
69
7/08
Table 25 Input Calibration Procedure
Step
Operation
Press
Result
1
Enter Calibration
Mode
Mode
SETUP
until you see
Upper Display
=
CAL
Lower Display
=
INPUT
FUNCTION
Upper Display
=
DIS
Lower Display
=
CAL IN
or
key
Upper Display
=
BEGN
Lower Display
=
CAL IN
2
Calibrate Zero (0%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
INZERO
•
Adjust the signal source to an output value equal to 0% range
value.
value.
•
Wait 5 seconds, then go to step 3.
3
Calibrate Span
(100%)
(100%)
FUNCTION
Upper Display
=
APLY
Lower Display
=
INSPAN
•
Adjust the signal source to an output value equal to 100%
range value.
range value.
•
Wait 5 seconds, then go to step 4.
4
FUNCTION
Calibration for zero and span input values are now saved. Input
calibration is complete.
calibration is complete.
NOTE: The display will automatically go to the CAL MOTOR set
up display. See Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.
up display. See Table 26. You may also exit calibation mode by
pressing the DISPLAY or SETUP keys.
ATTENTION:
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See Setting End-of-Travel
Limit Switches.
When calibrating the motor to a short stroke range, you must
reset the end-of-travel limit switches. See Setting End-of-Travel
Limit Switches.