IMPORTANT
When the T87F is used in a series 20 heating circuit 
(requires contact on both a rise and fall in tempera-
ture), set the anticipator indicator to 1.2.
If the current rating is not known, proceed as follows:
1. Connect an ac ammeter of appropriate range (for exam-
ple; 0 to 2A) between the R and W terminals on the 
wallplate, or between R and W on the subbase.
2. Let the system operate through the ammeter for at least 
one minute before taking the reading.
3. Set the heat anticipator to correspond to the ammeter 
reading (see Fig. 15).
4. A slightly higher setting to obtain longer burner-on times 
(and fewer cycles per hour) may be desirable in sys-
tems such as a one-pipe steam system. For example: 
• if burner on-time is too short with a heater setting of 
0.4, adjust to the 0.45 setting and check the system 
operation, then
• adjust to the 0.5 setting and recheck until the desired 
burner-on time is obtained.
OPERATION
CAUTION
Equipment Damage Hazard.
Improper installation can burn out thermostat heat 
anticipator.
On systems using a low voltage gas valve, do not 
apply a jumper across the valve coil terminals.
To check thermostat operation:
1. Turn down the temperature setting to the lowest point. 
2. If the subbase is used, move the system switch to the 
HEAT position. 
3. Raise the temperature setting until the burner starts. 
4. Slowly turn the dial back. (The burner should stop when 
the dial has been turned down below the room tempera-
ture.) 
5. If the T87F controls cooling, move the subbase system 
switch (if used) to COOL and lower the setting until the 
cooling equipment starts.
6. Raise the setting above the room temperature and the 
cooling system should shut down.
7. Make certain that the equipment functions properly in 
response to the thermostat.
RECALIBRATION
IMPORTANT
— If the thermostat scaleplate moves (pointer is station-
ary) when setting the temperature, the thermostat is 
a Group I model.
— If the scaleplate is stationary and the pointer moves, 
the thermostat is a Group II model.
The T87F is accurately calibrated at the factory under 
controlled conditions and no recalibration should be 
necessary. If it appears that the thermostat is out of 
calibration, make sure that it is level and is not subjected to 
radiant heat from the sun, radiators, or appliances.
Remove the thermostat cover ring so you can observe the 
mercury switch action. After a five- or ten-minute off-period 
(with thermostat setting below the room temperature), slowly 
raise the setting until the switch just makes contact. If the 
thermometer pointer and setting indicator read the same the 
instant you see the switch make, no recalibration is 
necessary. If recalibration is necessary, proceed as follows:
1. Turn the setting dial a few degrees above the room tem-
perature and remove the cover.
2. Slip the 104994 Calibration Wrench (available on 
request) onto the hex under the bimetal coil (see Fig. 
14).
3. Hold the dial firmly, and turn the hex counterclockwise 
for Group I models and clockwise for Group II models, 
until the mercury breaks contact.
4. Turn the dial to a low setting so that the thermostat 
loses the heat it has gained from your hands and its 
own operation.
5. Wait at least five minutes.
6. Slowly turn the dial until the pointers read the same.
7. Firmly hold the dial—carefully turning the hex clockwise 
for Group I models, counterclockwise for Group II mod-
els—until the mercury switch slips to the heating contact 
end of the tube.
8. Recheck the calibration, select the desired temperature 
and replace the cover.
NOTE: When the T87F provides cooling control, calibration 
for heating automatically calibrates for cooling.