Fujitsu DX90 S2 Manual Do Utilizador

Página de 80
Chapter 2  ETERNUS DX Disk Storage System Installation
  2.1  Installation Specifications
ETERNUS DX80 S2/DX90 S2 Disk storage system User’s Guide -Site Planning-
Copyright 2013 FUJITSU LIMITED
P3AM-4822-12ENZ0
29
2.1.2
ETERNUS DX90 S2
The following table shows the specifications of the ETERNUS DX90 S2.
Table 2.2    ETERNUS DX90 S2 installation specifications
Item
ETERNUS DX90 S2
2.5" drive configuration
3.5" drive configuration
Dimensions
(W × D × H)
Controller enclosure
482 × 645 × 88mm (2U)
482 × 670 × 88mm (2U)
Drive enclosure
482 × 540 × 88mm (2U)
482 × 555 × 88mm (2U)
Power 
distribution unit
1U
435 × 148 × 38mm
2U
(485 × 280 × 43mm) × 2 (*1)
Maximum 
weight (*2)
Controller enclosure
35kg
Drive enclosure
35kg
Power 
distribution unit
1U
2kg
2U
(6kg)  × 2 (*1)
Service area
Front: 800mm, Rear: 800mm
Power
Voltage
AC 100 – 120V, AC 200 – 240V
Phase
Single
Frequency
50Hz/60Hz
Number of power supply units
2 (for each enclosure)
Plug type
EMEA&I region
For AC200V connections:
IEC60320-C14G (supplied as standard)
Regions other 
than EMEA&I
For AC200V connections: 
NEMA L6-15P (supplied as standard)
For AC100V/AC200V connections:
IEC60320-C14 (optional)
Maximum power 
requirements 
(*2)
Controller 
enclosure
AC 100 – 120V
630W (640VA)
620W (630VA)
AC 200 – 240V
630W (640VA)
610W (620VA)
Drive 
enclosure
AC 100 – 120V
570W (580VA)
550W (560VA)
AC 200 – 240V
570W (580VA)
550W (560VA)
Maximum heat 
generation (*2)
Controller 
enclosure
AC 100 – 120V
2300kJ/h
2300kJ/h
AC 200 – 240V
2300kJ/h
2200kJ/h
Drive 
enclosure
AC 100 – 120V
2100kJ/h
2000kJ/h
AC 200 – 240V
2100kJ/h
2000kJ/h
Maximum 
amount of 
exhaust air
Controller enclosure
4.0m
3
/min
Drive enclosure
4.0m
3
/min