Vision Meter Operating Manual 
Singlephase & Network 
Vision Metering
 
 
Available Configurations 
The Vision singlephase/network meter is available in all standard utility configurations.  
Available forms include: 
 
Type 
Form 
Voltage 
Class 
K
TA 
V1S 
1S 
120V 
100 
1.0 
15 
V2S 
2S 
240V 
200 
1.0 
30 
V2S 
2S 
240V 
320 
1.0 
50 
V2SD 
2S 
120-480V 
200 
10.0 
30 
V3S 
3S 
240V 
20 
1.0 
2.5 
V3SD 
3S 
120-480V 
20 
1.0 
2.5 
V4S 
4S 
240V 
20 
1.0 
2.5 
V4SD 
4S 
120-480V 
20 
1.0 
2.5 
V12S 
12S 
120V 
200 
1.0 
30 
V12S 
12S 
120V 
320 
1.0 
50 
V12SD 
12S 
120-480V 
200 
10.0 
30 
Operating Parameters 
The  Vision  meter  is  fully  compliant  with  ANSI  C12.1,  C12.10  and  C12.20.    Operating 
parameters for the Vision meter are as follows: 
1.  Temperature-Operates  in  temperatures  between  -40C  to  +85C  within  the 
accuracy  limits  of  ANSI  C12.1  and  C12.20.    The  LCD  display  will  not  function 
below -25C but meter operation is unaffected and LCD operation resumes once 
temperature goes above -25C. 
2.  Humidity-Operates  normally  within  a  humidity  range  of  5  to  95%  (non-
condensing) 
3.  Voltage- Operating voltage for the Vision meter is nameplate voltage +/- 20%.  
For example, a 240V meter will operate normally from 192V to 288V. 
4.  Frequency-Vision meters operate normally at a rated frequency of 60Hz +/-5% 
5. 
Maximum current-Maximum allowable current is annotated by the Class rating 
on the meter nameplate.
 
Standard Operation 
The Vision meter ships pre-programmed from the factory ready for installation.  Meter settings 
and configuration can be modified after shipment using the Vision 20/20 software program.  No 
initial programming is required to begin using the meter under normal circumstances. 
 
When power is applied to the Vision meter, the startup sequence will commence.  The LCD will 
indicate the firmware version of the  meter for approximately 3 seconds.  This firmware version 
should be noted when modifying settings using our Vision 20/20 software because previous