3.5  EQUIPMENT CONNECTION  
3.5.1 GROUNDING CONNECTION 
 
Figure 24: MU Warning Lable 
 
3.5.2 MU GROUNDING CONNECTION 
Step  1:  Connect  the  GND  cable  to  the  GND  connector  and  the  building  EARTH.  Recommended  GND 
cable size is # 12 AWG. 
 
Step 2: Ensure the GND cable is connected to building GND. 
 
Grounding Connector
 
Figure 25: MU Grounding (MU Rear Panel) 
 
 
3.5.3 RU GROUNDING CONNECTION 
Step  1:  Connect  one  side  of  the  supplied  copper  wire  GND  cable  to  right  side  of  RU  with  two  M6×10 
hexagon Screws (screws are provided). Connect the other side of the supplied copper wire GND cable to 
the building EARTH with two M6 screws (screws are not provided). 
 
Step 2: Connect one side of the supplied copper wire GND cable to RU with two M6×10 hexagon Screws 
(screws  are  provided).  Connect  the  other  side  of  the  supplied  copper  wire  GND  cable  to  the  building 
EARTH with two M6 screws (screws are not provided). 
 
Step 3: Ensure all GND cables are well grounded to building GND. 
 
 
 
 
 
 
 
WARNING! 
This unit must always be grounded. Consult an appropriate electrical 
inspection authority or an electrician if you are uncertain that suitable 
grounding is available.
  
 
Do not connect power before grounding.