Peter Electronic VD 075/E2 1-phase frequency inverter, to , 2I000.23075 2I000.23075 Ficha De Dados
Códigos do produto
2I000.23075
15
IO processor software version
03
Read Only
16
Motor control processor software
version
version
03
Read Only
17
Drive type
03
Read Only
18
Reserved
03
Read Only
19
Reserved
03
Read Only
20
Analog 1 input result
03
Read Only
21
Analog 2 input result
03
Read Only
22
Speed reference value
03
Read Only
23
DC bus voltages
03
Read Only
24
Drive temperature
03
Read Only
25 to 30
Reserved
03
Read Only
Control and Status Register Descriptions
Read and write registers
Register 1: Drive command
Register 1: Drive command
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
High byte
Low byte
Bit 0: Run/Stop command: Set to 1 to enable the drive. Set to 0 to stop the drive.
Bit 1: Fast stop request. Set to 1 to enable drive to stop with 2
nd
deceleration ramp.
Bit 2: Reset request. Set to 1 in order to reset the drive if drive is under trip condition.
User must clear this bit when drive is under normal condition to prevent un-expected reset.
Bit 3: Coast stop request. Set to 1 to issue a coast stop command.
For normal operation, Bit 3 has the highest priority, bit 0 has the lowest priority (bit 3>bit 1>bit 0). For example
if user set command as 0x0009, drive will do a coast stop rather than run. For normal run/start, just set this
register to 1.
Note that stat/stop(bit 0), fast stop(bit 1) and coast stop(bit 3) only works if P-31= 0 or 1. Otherwise, start/stop
function is controlled by drive control terminals. Reset function(bit 2) works all the time as long as drive is
operated under Modbus control mode (P-12=3 or 4).
Register 2: speed reference setup
This register holds the speed reference value. The input data is 16bits integer and it also includes one decimal
place. For example, value 500 represents the 50.0Hz, value 123 gives 12.3Hz. To get negative speed reference,
user needs put negative value into this register. For example, -1(0xFFFF) gives -0.1Hz. -234(0xFF16) gives -
23.4Hz.
The input value range from -5000 (0 for single phase output drive) to +5000, however the drive output speed
will be limited by the maximum speed set by P-01.
Register 4: Modbus ramp control time
This register specifies the drive acceleration and deceleration ramp time. User can only write to this register
when P-12 is set to 4. The input data range is from 0 to 60000 (0.00s to 600.00s)