PID is easy 
 
8.2 PID_Compact instruction 
 
Easy Book 
174
 
Manual, 03/2014, A5E02486774-AF 
Parameter and type 
Data type 
Description 
ManualEnable 
IN 
Bool 
Enables or disables the manual operation mode. (Default value: 
FALSE): 
 
A FALSE to TRUE edge activates "manual mode", while State = 4, 
Mode remains unchanged. 
As long as ManualEnable = TRUE, you cannot change the 
operating mode using a rising edge at ModeActivate or use the 
commissioning dialog. 
 
A TRUE to FALSE edge activates the operating mode that is 
assigned by Mode. 
Note: We recommend that you change the operating mode using 
ModeActivate only. 
ManualValue 
IN 
Real 
Output value for manual operation. (Default value: 0.0) 
You can use values from Config.OutputLowerLimit to 
Config.OutputUpperLimit. 
ErrorAck 
IN 
Bool 
Resets the ErrorBits and warning outputs. FALSE to TRUE edge 
Reset 
IN 
Bool 
Restarts the controller. (Default value: FALSE): 
 
FALSE to TRUE edge: 
–  Switches to "inactive" mode 
–  Resets the ErrorBits and warning outputs 
–  Clears Integral action 
–  Maintains PID parameters 
 
As long as Reset = TRUE, PID_Compact remains in "Inactive" 
mode (State = 0). 
 
TRUE to FALSE edge: 
–  PID_Compact switches to the operating mode that is saved in 
the Mode parameter. 
ModeActivate 
IN 
Bool 
The PID_Compact switches to the operating mode that is saved in the 
Mode parameter. FALSE to TRUE edge: 
Mode 
IN 
Int 
The desired PID mode; Activated on the leading edge of the Mode 
Activate input. 
ScaledInput 
OUT 
Real 
Scaled process value. (Default value: 0.0) 
Output
1
 
OUT 
Real 
Output value in REAL format. (Default value: 0.0) 
Output_PER
1
 
OUT 
Word 
Analog output value. (Default value: W#16#0) 
Output_PWM
1
 
OUT 
Bool 
Output value for pulse width modulation. (Default value: FALSE) 
On and Off times form the output value. 
SetpointLimit_H 
OUT 
Bool 
Setpoint high limit. (Default value: FALSE) 
If SetpointLimit_H = TRUE, the absolute setpoint upper limit is reached 
(Setpoint ≥ Config.SetpointUpperLimit). 
The setpoint is limited to Config.SetpointUpperLimit. 
SetpointLimit_L 
OUT 
Bool 
Setpoint low limit. (Default value: FALSE) 
If SetpointLimit_L = TRUE, the absolute setpoint lower limit is reached 
(Setpoint ≤ Config.SetpointLowerLimit). 
The setpoint is limited to Config.SetpointLowerLimit. 
InputWarning_H 
OUT 
Bool 
If InputWarning_H = TRUE, the process value has reached or 
exceeded the warning high limit. (Default value: FALSE)