8.4 PID_3Step instruction 
 
Easy Book 
180
 
Manual, 03/2014, A5E02486774-AF 
Table 8- 7 
Data types for the parameters 
Parameter and type 
Data type 
Description 
Setpoint 
IN 
Real 
Setpoint of the PID controller in automatic mode. (Default value: 0.0) 
Input 
IN 
Real 
A tag of the user program is used as the source of the process value. 
(Default value: 0.0) 
If you are using the Input parameter, you must set 
Config.InputPerOn = FALSE.  
Input_PER 
IN 
Word 
An Analog input is used as the source of the process value. (Default 
value: W#16#0) 
If you are using the Input_PER parameter, you must set 
Config.InputPerOn = TRUE.  
Actuator_H 
IN 
Bool 
Digital position feedback of the valve for the high end stop 
If Actuator_H = TRUE, the valve is at the high end stop and is no longer 
moved in this direction. (Default value: FALSE) 
Actuator_L 
IN 
Bool 
Digital position feedback of the valve for the low end stop 
If Actuator_L = TRUE, the valve is at the low end stop and is no longer 
moved in this direction. (Default value: FALSE) 
Feedback 
IN 
Real 
Position feedback of the valve. (Default value: 0.0) 
If you are using the Feedback parameter, you must set 
Config.FeedbackPerOn = FALSE.  
Feedback_PER 
IN 
Int 
Analog feedback of the valve position. (Default value: W#16#0) 
If you are using the Feedback_PER parameter, you must set 
Config.FeedbackPerOn = TRUE. Feedback_PER is scaled, based upon 
the following tags: 
 
Config.FeedbackScaling.LowerPointIn 
 
Config.FeedbackScaling.UpperPointIn 
 
Config.FeedbackScaling.LowerPointOut 
 
Config.FeedbackScaling.UpperPointOut 
Disturbance 
IN 
Real 
Disturbance variable or pre-control value 
ManualEnable 
IN 
Bool 
Enables or disables the manual operation mode. (Default value: 
FALSE): 
 
A FALSE to TRUE edge activates "manual mode", while State = 4, 
Mode remains unchanged. 
As long as ManualEnable = TRUE, you cannot change the 
operating mode using a rising edge at ModeActivate or use the 
commissioning dialog. 
 
A TRUE to FALSE edge activates the operating mode that is 
assigned by Mode. 
Note: We recommend that you change the operating mode using 
ModeActivate only. 
ManualValue 
IN 
Real 
Process value for manual operation. (Default value: 0.0) 
In manual mode, you specify the absolute position of the valve. 
ManualValue is evaluated only if you are using OutputPer, or if position 
feedback is available.