Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 Manual Do Utilizador

Códigos do produto
6AV6651-7KA01-3AA4
Página de 364
 
Motion control is easy 
 
10.5 Motion control instructions 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
219
 
Parameter and type 
Data type 
Description 
Status 
OUT 
Bool 
Status of axis enable:  
 
FALSE: The axis is disabled: 
–  The axis does not execute motion control tasks and does not 
accept any new tasks (exception: MC_Reset task). 
–  The axis is not homed. 
–  Upon disabling, the status does not change to FALSE until the 
axis reaches a standstill. 
 
TRUE: The axis is enabled: 
–  The axis is ready to execute motion control tasks. 
–  Upon axis enabling, the status does not change to TRUE until 
the signal "Drive ready" is pending. If the "Drive ready" drive 
interface was not configured in the axis configuration, the status 
changes to TRUE immediately. 
Busy 
OUT 
Bool 
FALSE: MC_Power is not active. 
TRUE: MC_Power is active. 
Error 
OUT 
Bool 
FALSE: No error 
TRUE: An error has occurred in motion control instruction "MC_Power" 
or in the associated technology object. The cause of the error can be 
found in parameters "ErrorID" and "ErrorInfo". 
ErrorID 
OUT 
Word 
Error ID for parameter "Error"" 
ErrorInfo 
OUT 
Word 
Error info ID for parameter "ErrorID" 
 
 
An axis is enabled and then disabled again. After the drive has signaled "Drive ready" back to the CPU, the 
successful enable can be read out via "Status_1". 
 
Following an axis enable, an error has occurred that caused the axis to be disabled. The error is eliminated and 
acknowledged with "MC_Reset". The axis is then enabled again.