Technical specifications 
 
A.8 RTD and Thermocouple modules 
 
Easy Book 
320
 
Manual, 03/2014, A5E02486774-AF 
Technical data 
SM 1231 AI 4 x RTD x 16 bit 
SM 1231 AI 8 x RTD x 16 bit 
Number of inputs (Page 323)  
Type 

Module-referenced RTD and Ω 

Module-referenced RTD and Ω 
Diagnostics 
 
Overflow / underflow 
2,3
 
 
24 VDC low voltage 
2
 
 
Wire break (current mode only) 
4
 
 
Overflow / underflow 
2,3
 
 
24 VDC low voltage 
2
 
 
Wire break (current mode only) 
4
 
 
1
  20.4 to 28.8 VDC (Class 2, Limited Power, or sensor power from CPU) 
2
  The overflow, underflow and low voltage diagnostic alarm information will be reported in the analog data values even if 
the alarms are disabled in the module configuration. 
3
  For resistance ranges underflow detection is never enabled. 
  When wire break alarm is disabled and an open wire condition exists in the sensor wiring, the module may report 
random values.