Westinghouse WER080C2X045 Instrução De Instalação

Página de 23
 
 
                                                                                   WHL-003 REV. 7.14.14 
 
ELEMENT KIT  
PART # 
# ELEMENTS 
AND 
THERMOSTATS 
AVAILABLE 
WATTAGE 
VOLTAGE  
FULL LOAD CURRENT IN 
AMPS 
Single Phase 
C2X030 
3,000 
240 
13 
C2X045 
4,500 
19 
Table 2 
– Listing of Elements and Corresponding Voltages / Wattages / Amperages 
C. LOCATING THE WATER HEATER 
 
Locate the water heater where any leakage from the relief valve, related piping, tank, or connections will not result in damage to 
surrounding areas or lower floors of the building. The water heater should be located near a floor drain, or installed in a drain pan. 
Westinghouse WILL NOT be held liable for leakage damages. 
 
 
 
Incorrect ambient conditions can lead to damage to the heating system and 
put safe operation at risk. Ensure that the installation location adheres to the 
information included in this manual. Failure to do so could result in property 
damage, serious personal injury, or death. 
 
 
Failure of water heater or components due to incorrect operating conditions 
IS NOT covered by product warranty. 
 
1. Installation Area (Mechanical Room) Operating Conditions 
 
Ensure ambient temperatures are higher than 32
o
F/0
o
C and lower 
than 104
o
F/40
o
C. 
 
Avoid continuously high levels of humidity 
 
Never close existing ventilation openings 
 
 
 
 
 
The service life of the water heater’s exposed metallic surfaces, such as the junction box, is directly influenced by proximity to damp 
and salty marine environments. In such areas, higher concentration levels of chlorides from sea spray coupled with relative humidity 
can lead to degradation of water heater components. 
 
 
This water heater is certified for indoor installations only. Do not install the water heater outdoors. Outdoor installations ARE NOT 
covered by warranty. Failure to install this water heater indoors could result in substantial property damage, severe personal injury, or 
death. 
 
2. Check for nearby connections to: 
 
System water piping 
 
Electrical power 
Choose a location for the water heater as centralized to the piping system as possible. 
 
3. Check area around water heater. Remove any combustible materials, gasoline, and other flammable liquids. 
 
 
This water heater must not be located near flammable liquids such as gasoline, butane, liquefied propane, adhesives, solvents, paint 
thinners, etc., as the controls of this water heater could ignite these vapors and cause an explosion, resulting in property damage, 
severe personal injury, or death. 
 
4. If the water heater is to replace an existing water heater, check for and correct any existing system problems, such as: 
 
System leaks 
 
Location that could cause the system and water heater to freeze and leak. 
Figure 2 
– Recommended Clearances