Vaillant VRT 360f Operating and Guia De Utilização

Página de 48
30
Installation instructions VRT 360f
8.2 Regulations
Use standard commercial cables for 
wiring.
-  Minimum cross-section of the wires:
0.75 mm
2
Do not exceed following maximum wire 
lengths:
- Bus lines: 300 m
Connection lines at 230 V and bus wires 
must be laid separately when longer 
than 10 m.
The room temperature thermostat may 
only be installed in dry rooms.
All wiring must be in accordance with 
Building Regulations Part P and BS 7671 
(IEE Wiring Regulations), and must be 
carried out by a suitably qualified per-
son.
8 Safety instructions and regulations