JKSSS+ Series - 62
JKSSS+ Series   
 
 
 
 
           
            
   2.3 - 4.2KV
SP.8 Overload Curve Configuration (Setpoint Page 8)
(Security Level: 3)
SP8.3 Area Under Curve Protection: If enabled, this 
secondary start protection uses both the basic start 
protection and the area under the curve protection.
 
•  Max I*I*T Start: The maximum I
2
T allowed during 
start.  If the I
2
T to start exceeds this number then the 
soft starter will generate a trip. 
SP8.4 Current Over Curve: Learns the motor’s starting 
characteristics and protects the motor based upon 
the learned curve. It is useful when commissioning a 
new motor.
  Learn: The unit reads the motor’s starting 
characteristics. Start the motor and allow it to come 
to full speed. The start feedback enables the motor 
protection based on the learned start curve.
•  Learned Start Curve Basis: The maximum allowed 
deviation above or below the start curve before a trip 
is generated.
•  Time for Sampling: The time the soft starter 
continues to sample the start curve characteristic 
during learn the mode.
MENU
PAGE 8    OVERLOAD
CURVE CONFIGURATION
BASIC RUN
OVERLOAD CURVE
(Hit DOWN ARROW seven times)
RUN CURVE LOCKED
ROTOR TIME: O/L CLASS
Range: 1 - 30 SEC, O/L CLASS
RUN LOCKED ROTOR
CURRENT:  600% FLA
BASIC START 
OVERLOAD CURVE
AREA UNDER CURVE
PROTECTION: DISABLED
CURRENT OVER
CURVE: DISABLED
Range: ENABLED or DISABLED
Options: DISABLED, LEARN
                or ENABLED
COAST DOWN TIMER
TIME:  DISABLED
START CURVE LOCKED
ROTOR TIME: O/L CLASS
NUMBER OF STARTS PER
HOUR:   DISABLED
TIME BETWEEN STARTS
TIME:  5 MIN
MAX I*I*T START
: 368 FLA*FLA*SEC
ACCELERATION TIME
LIMIT:  30 SEC
LEARNED START CURVE
BIAS:  10%
Range:1 - 60 MIN, DISABLED
Increments of 1
Range:1 - 30 SEC, O/L CLASS
Increments of 1
Range:1 - 300 SEC, DISABLED
Increments of 1
Range: 1 - 6, DISABLED
Increments of 1
Range:1 - 60 MIN, DISABLED
Increments of 1
Range:1 - 2500, FLA*Time (Sec)
Increments of 1
Range: 5 - 40%
Increments of 1
START LOCKED ROTOR
CURRENT:  600% FLA
TIME FOR SAMPLING
: 30 SEC
Range: 400 - 800%
Increments of 10
Range: 1 - 300 SEC
Increments of 1
Range: 400 - 800%
Increments of 1
Configures the unit’s start and
run protection mode. The unit has
independent start and run curve
protection and the settings can be
based on the OL Class or set by the
motor’s locked rotor current and time.
SP8.1 Basic Run Overload Curve
•  Run Curve Locked Rotor
 Time: Set the locked rotor time
 
  to the OL Class default chosen
 
  in Setpoint Page 1 or set the
 
  time in seconds. This is the
 
  time the locked rotor condition
 
  exists before a trip occurs. 
 
•  Run Locked Rotor Current:
 
  The current the motor draws
 
  with full voltage on the windings
 
  and no rotor movement (as a
 
  percent of motor FLA). Refer to
 
  the nameplate data or contact
 
  the motor manufacturer. 
•  Coast Down Timer: If enabled,
 
  this prevents the motor from
 
  restarting for the programmed
 
  amount of time, after a stop
 
  command is given.
SP8.2 Basic Start Overload Curve
•  Start Curve Locked Rotor Time: The locked 
rotor time can be set to the OL Class default 
chosen in Setpoint Page 1 or  to a specific 
time. The overload condition must exist for the 
programmed amount of time before a trip occurs.
•  Start Locked Rotor Current: The current the 
motor draws with full voltage on the windings and 
no motor movement (as a percent of motor FLA). 
Refer to the motor nameplate data or contact the 
motor manufacturer. 
•  Acceleration Time Limit: If the motor does not 
enter run mode (reach at speed) within the preset 
time, the unit trips on acceleration time limit.  
•  Number of Starts per hour: If enabled, this  
limits the maximum number of starts permitted per 
hour. This setpoint allows a maximum of 6 starts 
per hour. Contact motor manufacturer. 
•  Time Between Starts: If enabled, the soft 
starter prevents another start attempt until the 
programmed time has expired.