page 22 — dca70SSJU4i 60 hz generator • operation and parts manual — rev. #2 (04/09/14) 
eNGiNe/GeNeratOr CONtrOL paNeL
The definitions below describe the controls and functions 
of the Engine/Generator Control Panel (Figure 7).
1. 
gauge Unit assembly — This assembly houses the 
various engine monitoring gauges. These gauges  
indicate: oil pressure, water temperature, charging 
voltmeter, fuel and engine speed RPM (tachometer).
A. 
Oil pressure gauge — During normal operation 
this gauge be should read between 35 to 65 psi. 
(241~448 kPa). When starting the generator the 
oil pressure may read a little higher, but after the 
engine warms up the oil pressure should return to 
the correct pressure range.
B. 
Water Temperature gauge — During normal 
operation this gauge be should read between 185° 
and 207°F (85°~97°C).
C. 
charging voltmeter  gauge  — During normal 
operation this gauge indicate minimum 14 VDC
D. 
Fuel gauge — Indicates amount of diesel fuel 
available.
E. 
Tachometer — Indicates engine speed in RPM’s 
for 60 Hz operation. This meter should indicate 
1800 RPM’s when the rated load is applied.
2. 
Fuel leak detected alarm lamp — This lamp  when 
ON indicates that fluids in the containment area have 
reach a high level.
3. 
panel light switch — When activated will turn on 
control panel light.
4. 
panel  light  — For operation at night, panel light 
illuminates control panel for ease of reading meters 
and gauges. Make sure panel light switch is in the OFF 
position when light is not in use.
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
VOLTS
BATTERY
6
12
18
24
30
°F
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
D
A
B
C
E
1
OFF
W
U
V
OFF
W-U
V-W
U-V
DECREASE
INCREASE
PSI
OIL PRESS
0
25
50
75
100
°F
WATER TEMP
100
140
180
220
260
VOLTS
BATTERY
6
12
18
24
30
FUEL
E
½
F
RPMX10
SPEED
0
120
150
180
210
60
Series 800 Controller
ECU
Engine Started
Shutdown
Pre-Alarm
Alarm
Acknowledge
Screen
Change
Program
Exit
Option
2
3
4
5
6
7
8
9
10
11
12
13
Figure 7. Engine/Generator Control Panel
5. 
Frequency meter — Indicates the output frequency 
in hertz (Hz). Normally 60 Hz
6. 
ac ammeter — Indicates the amount of current the 
load is drawing from the generator per leg selected by 
the ammeter phase-selector switch.
7. 
ac voltmeter — Indicates the output voltage present 
at the 
u,v, and W output terminal lugs.
8. 
voltage regulator control — Allows ±15% manual 
adjustment of the generator’s output voltage.
9. 
ammeter change-over switch — This switch allows 
the AC ammeter to indicate the current flowing to the load 
connected to any phase of the output terminals, or to be 
switched off. This switch does not effect the generator 
output in any fashion, it is for current reading only. 
10. 
voltmeter change-over switch — This switch allows 
the AC voltmeter to indicate phase to phase voltage 
between any two phases of the output terminals or to 
be switched off.
11. 
main circuit Breaker — This three-pole, 200 amp 
main breaker is provided to protect the 
u,v, and W 
output terminal lugs from overload.
12. 
auto/start switch — This switch selects either manual 
or automatic operation . Center position is OFF (reset).
13. 
hour check Button — With the engine stopped, press 
and hold this button. The total running hours, fuel level, 
and battery voltage will be displayed.