Honeywell Work Light DR4300 Manual Do Utilizador
Installation
12/03
DR4300 Circular Chart Recorder Product Manual
43
2.6.3 Transmitter Power Out
Introduction
A recorder model is available that provides +24 Vdc power out to a transmitter.
Procedure
Refer to Figure 2-17 and follow the procedure in Table 2-15 to wire the transmitter power out.
Table 2-15 Transmitter Power Out Wiring
Step Action
ATTENTION To avoid damaging the recorder, be sure that you install the power wires into the
correct screw terminals as shown in Figure 2-9 and Figure 2-10.
correct screw terminals as shown in Figure 2-9 and Figure 2-10.
1
Turn off the power to the recorder.
2
Open the recorder door. Loosen the captive screw in the chart plate and swing the plate out.
3
Locate the DC OUT terminal block on the Transmitter Power Module, located above the
printed circuit assembly (PCA) for pen 1. (See Figure 2-17.)
printed circuit assembly (PCA) for pen 1. (See Figure 2-17.)
4
Run the output wires through the appropriate conduit hole (see Figure 2-7 and Figure 2-8).
Refer to Table 2-6 for acceptable wire bundling.
Refer to Table 2-6 for acceptable wire bundling.
5
Strip 1/4-inch maximum of insulation from the end of each wire and form end to fit under a
screw connection.
screw connection.
6
Insert the wires under the appropriate screws for the transmitter power out as shown in the
figure. Tighten the screws to secure the wires.
figure. Tighten the screws to secure the wires.