Use                 arrows to set maximum voltage point for Battery Trouble alarm.  Press            to confi rm.
SETTINGS
ALARM LIMITS
1
MAX
Use                 arrows to set minimum voltage point for AC Voltage Low alarm.  Press            to confi rm.
SETTINGS
ALARM LIMITS
1
V  MIN
Use                 arrows to set maximum voltage point for AC Voltage High alarm.  Press            to confi rm.
SETTINGS
ALARM LIMITS
1
V  MAX
ENABLED
Use                 arrows to enable or disable the AC Voltage High alarm.  Press            to confi rm.
1
ENABLED
Use                 arrows to enable or disable the AC Voltage Low alarm.  Press            to confi rm.
1
SETTINGS
ALARM LIMITS
1
COIL CHECK
Use                 arrows to set monitoring of the engine starting solenoid coils (1-, -2, 1&2, OFF).  Press            to confi rm.
Settings - Feature Settings
SETTINGS
FEATURE SETTINGS
1
AC POWER LOSS START
ENABLED
Use                 arrows to enable or disable the AC Voltage Loss Start feature.  Press            to confi rm.
1
DELAY
Use                 arrows to set the time delay between loss of AC voltage and engine starting (0-60 sec.).  
Press            to confi rm.
SETTINGS
FEATURE SETTINGS
1
INTERLOCK ALARM
Use                 arrows enable or disable the alarm for Interlock On.  Press           to confi rm.
SETTINGS
FEATURE SETTINGS
1
LOW PRESSURE AUD
Use                 arrows enable or disable the audible alarm for Low System Pressure.  Press           to confi rm.
11
Use                 arrows to enable or disable the alarm for Low Suction Pressure.  Press            to confi rm.
SETTINGS
FEATURE SETTINGS
LOW SUCTION
1
AUDIBLE
Use                 arrows to enable or disable the audible alarm for Low Suction Pressure.  Press            to confi rm.
1
COMMON ALARM
Use                 arrows to enable or disable the common alarm output (ALR relay) for Low Suction Pressure.  
Press            to confi rm.
1
PUMP ROOM
Use                 arrows to select the alarm output relay for Low Suction Pressure (Disabled, PTR (Pump Room Trouble), ETR 
(Engine Trouble), Both PTR and ETR).  Press            to confi rm.
1
ENABLE
SETTINGS
FEATURE SETTINGS
MAIN SWITCH MIS-SET
1
Use                 arrows to choose how the Main Switch Mis-Set alarm relay operates.  “Pick Up” means the relay will ener-
gize when the switch is not in auto.  “Drop Out” means the relay we de-energize when the switch is not in auto. 
Press            to confi rm.