Weil-McLain PLUS LINE PLUS-E017-A/1206 Manual Do Utilizador

Página de 68

Part Number PLUS-E017-A/1206
PLUS LINE
 Indirect-Fired Water Heaters – Series 3
Installation and start-up of 
water heaters connected to 
steam boilers
See Figure 29, page , for suggested piping schematic.
Pipe the domestic water connections to the water heater
per Section A of this manual.
•  Boiler  connections  for  the  water  heater  must  be
below the water line.
•  For steam piping, refer to the boiler manual.
•  Replace the automatic air vent furnished with the
water heater with a manual air vent.
•  Wire the water heater and circulator to the boiler
per suggested wiring in Figure 29.
To fill the boiler and water heater:
•  Close isolation valves  and  (Figure 29) to isolate
the boiler.
•  Fill the boiler to the recommended water level per
the boiler manual. Fill the domestic side of the water
heater per Section A of this manual.
•  To fill the water heater outer tank with boiler water,
isolation valves  and  must remain closed. Valves
1 and 2 should be fully opened. Drain valves  and
 should also be fully opened.
•  Open the water heater manual air vent to bleed the
system of air.
Open the water heater manual air
vent one turn only.
•  Fill the boiler/water heater system through drain
valve  until a steady stream of water flows through
drain valve , initially purging the system of air.
•  Continue to fill the boiler/water heater system while
closing drain valve .
•  When  drain  valve    is  fully  closed  and  a  steady
stream of water is exiting at the air vent, close the
manual air vent tightly. Drain valve  can now be
closed.
Water may spray from the manual
air vent.
•  Open isolation valve  (at the front of the boiler).
Then open valve .
•  Start the boiler per instructions given in the boiler
manual.
Connecting water heater to 
steam boiler
When  designing  steam  and  domestic  hot  water  sys-
tems,  there  are  some  key  issues  that  must  be  taken
into consideration during the initial design phase. By
designing the system properly from the start, you can
avoid problems and have a hot water loop in a steam
boiler system.
Special considerations:
•  Keep the loop temperature below the flash point.
Flashing can result in noise and circulator damage
or shortened life.
•  Be sure the loop is completely closed, with no au-
tomatic air vents or anything that could allow air
to enter the system when the pump shuts off. Use
manual air vents only to prevent the possibility of
flooding the boiler.
•  Pipe supply from one side of the boiler, return to
the opposite side.
•  Supply  from  a  tapping  that  is  high  enough  to
prevent introducing sediment into the piping and
circulator yet still positions the circulator below the
water line. Avoid the mud leg of the boiler.
•  Use an all bronze circulator (avoid wet rotor circula-
tors). This will reduce clogging and will resist the
corrosion potential from the steam condensate.
•  Make  sure  the  circulator  is  properly  sized.  If  the
pump  runs  too  far  out  on  the  curve,  cavitation
potential increases significantly.
•  Return  piping  should  be  dedicated  domestic  re-
turn.
•  Use (2) flow/check valves as shown to reduce the
potential for gravity circulation. Do not use spring-
loaded check valves in place of the flow/check valves
shown in Figure 29 on page .
ON STEAM BOILER APPLICATIONS ONLY — You must replace the automatic air vent
supplied with the water heater with a manual air vent. Failure to do so could result in severe
personal injury, death or substantial property damage.
Boiler-side piping 
(except 
 Gas)
 
continued
C