Emerson Smart Control Modules Instrução De Instalação
4
DOC.IG.QC01.1 Rev.: B
December ‘06
En
4 Electric Connections
4.1 Electrical data Control Modules
QC01 - 24VDC
Power supply input:
Voltage
Voltage
24VDC (±15%)
Maximum current
125 mA
Power (nominal)
2.5 W
Control signal input:
Voltage
Voltage
24VDC (±15%)
Maximum current
5mA
max.
Contacts
Potential free
Feedback outputs:
Voltage
Voltage
0-30 VDC
Current DC
500mA (maximum)
1 mA (advised minimum)
1 mA (advised minimum)
Resistance (nom.) 0.5 Ohm (On state)
Maximum power
Maximum power
15W
Electric contacts
Potential free
Temperature *
-20°C to +80°C
(-4°F to +176°F)
(-4°F to +176°F)
QC03 - IS
QC04 - IS-N
Power supply input:
Voltage
Voltage
13.5 - 27.6 V
13.5 - 27.6 V
Maximum current
68 mA
68 mA
Maximum Power
1.2 W
1.2 W
Capacity Ci (max.) 15 nF
15 nF
Inductivity Li
0 mH
0 mH
Control signal input:
Voltage
Voltage
6 - 30 V
6 - 30 V
Maximum current
5 mA
5 mA
Capacity Ci (max.) 3.2 nF
3.2 nF
Inductivity Li
0 mH
0 mH
Contacts
Potential free Potential free
Feedback outputs:
Maximum voltage 30 VDC
Maximum voltage 30 VDC
IEC 60947-5-6
Maximum current
32 mA
IEC 60947-5-6
Resistance (nom.) 440 Ohm
440 Ohm
Switch resistance
300kOhm
10440 Ohm
(off-state)
Maximum power
Maximum power
1.2 W
IEC 60947-5-6
Electric contacts
Potential free IEC 60947-5-6
Temperature *
-20°C to +50°C
(-4°F to +122°F)
(-4°F to +122°F)
Polarity:
Dependent
Dependent
Power supply
Independent
Control signal + feedback switches
Environmental conditions :
Humidity
Humidity
0 to 85% at 25°C(+77°F) derate to 50% above 40°C(104°F) (non-condensing).
Altitude
Operating full power available up to 2000 meter (6000 feet).
Use
In- and outdoor.
*
In case the Control Modules are used in
Hazardous locations, check the Control
Drawings as per chapter 4.2 for the applicable
temperature range.
Hazardous locations, check the Control
Drawings as per chapter 4.2 for the applicable
temperature range.
4.2
Electrical data of the hazardous
area executions
area executions
Please check the following chapters for electrical
data and instructions in case an approved Control
Module is used in a hazardous location:
Non Incendive/Non Sparking
-
data and instructions in case an approved Control
Module is used in a hazardous location:
Non Incendive/Non Sparking
-
QC01 24VDC
Chapter 10
Intrinsically safe
-
-
QC03 IS
Chapter 11
-
QC04 IS-NAMUR
Chapter 12