Advanced Troubleshooting
IMPORTANT
 THIS SECTION IS INTENDED FOR QUALIFIED REFRIGERATION SERVICE TECHNICIANS ONLY.
THE TECHNICIAN SHOULD REPEAT ALL OF THE PREVIOUS TROUBLESHOOTING STEPS
BEFORE TAKING ACTION ON THESE MORE TECHNICAL SOLUTIONS.
Evaporator Coil is Freezing
Possible Cause
Solution
Charge too low
Check sight glass
Check for leaks
Add refrigerant
TXV malfunctioning
Repair or replace
High Pressure Switch Keeps Tripping Even After Checking for
Obstructions and Dirty Filters/Coils
Possible Cause
Solution
Condenser fan not operating
Repair or replace
Defective switch
Replace
Unit Cycles On and Off More than 8 times/hr.
Possible Cause
Solution
Thermostat malfunctioning
Check the thermostat guide for
thermostat information
Low suction pressure
Check low pressure switch
Check pressure and adjust superheat
High Pitched or Loud Rubbing Noise, Clanking or Vibration
Possible Cause
Solution
Fans loose or malfunctioning
Repair  or replace
Excessive compressor vibration
Replace
TXV malfunctioning
Repair or replace
Replacing the Blowers
 When replacing the fan or motor, replace the fan and motor as a unit. Do
not remove the motor from the impeller wheel.