RoboteQ AX2550 Manual Do Utilizador

Página de 186
AX1500 Motor Controller User’s Manual
153
Counter Read Data Format
Counter Read Data Format
When receiving a counter read query, the encoder module will output the value of its 32-bit 
counter. If all 32-bit are sent, this would require 8 ASCII digits to represent the value. 
A 32-bit counter can store over 2 billion counts in each direction. In practice, it will be rare 
that counts will be so large than only a partial number of the counter’s bits will be signifi-
cant at any given time.
In order to create a more efficient data stream on the controller’s serial port, a simple com-
pression technique is implemented. The scheme eliminates all of the counter’s most signif-
icant bits if they are at 0 (for a positive count number) or F (for a negative count number). 
For example, if the counter value is Hex 00000015, the value 15 will be returned after a 
counter query. 
For negative numbers, a count value of -5 (which is FFFFFFFB in hex), the response to the 
query will be B. 
To distinguish between positive and negative numbers, the Encoder module will insert a 0 
ahead of any number string starting with a digit value higher than 7 (i.e. 8 to F) to signify 
that the number is positive. For negative numbers, the Encoder module will insert an F 
ahead of any number string starting with a digit value lower than 8 (i.e. 0 to 7). The table 
below shows examples of this scheme as applied to various counter values.
When reading the counter value into a microcomputer, the reverse operation must take 
place: any output that is less than 8 digit long must be completed with a string of 0’s if the 
first digit is of value 0 to 7, or with a string of F’s if the first digit is of value 8 to F.
The resulting Hex representation of a signed 32-bit number must then be converted to 
binary or decimal as required by the application.
The burden of this extra processing is more than offset by the bandwidth relief on the con-
troller’s serial port. 
Encoder Testing and Setting Using the PC Utility
Extensive diagnostic, calibration, setting and testing support is provided in the Roborun PC 
utility. Basic instructions on how to install and run the PC utility can be found in “Using the 
Roborun Configuration Utility” on page 161
TABLE 29. Example counter values and RS232 output using a reduction scheme
Decimal
32-bit Hex
Controller Output
+5
00000005
5
+250
000000FA
0FA
-6
FFFFFFFA
A
-235
FFFFFF15
F15
+91,011,186
056CB872
56CB872
-7,986,091
FF862455
862455