PAGE 26                                                         06 Apr 2000                            CH. 4:  TIU110/111/112/113
GFK-1819
4.5.1 
TIU11X Configuration of the RS-485 Port
The configuration bank (shown in Figure 4.8) sets the parameters of the RS-485 port as described in
Table 4.1.
Table 4.1 – Configuration Bank
Switch 1
ON: Pull-up (must be used together with switch 3)
OFF: no Pull-up
Switch 2
ON: 120
Ω
 termination
OFF: no termination
Switch 3
ON: Pull-down (must be used together with switch 1)
OFF: no Pull-down
Switch 4
Reserved for future use
NOTE: Switch 1 and 3 must be used together.  Either both pull-up and pull-down are
used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus.  This is useful if
there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120
Ω
 must be placed across each end of the RS-485 bus.  With switch 2 ON,
a 120
Ω
 resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last
device at either end of the bus.
4.6 TIU11X 
Dimensions
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE
TIU11X CUTOUT DETAILS
3.27”       [83     mm]
+ 0 .0 2
-0 .0 0
+ 0 .5
-0 .0
5.95” [151m m]
UP TO 0.04”[1mm] CORNER
RADIUS IS ACCEPTABLE
Figure 4.8 – TIU11X Cutout