MGE UPS Systems 12280 kVA Manual Do Utilizador

Página de 13
MGE UPS SYSTEMS
CleanWave - Installation and user manual
Page 5/13
Version 2.1 - 21/04/05 - (JME)
2.2. R
ANGE
The following table summarises the characteristics of the different products of the range (at 400V,
50/60Hz).
Minimum sections 
1
TYPE
Power.
I
phase
max
I
neutral
Max
Total
losses
max
Phases
Neutral (N)
Earth (PE)
( PEN 
2
 )
[kVA]
[A]
[A]
[W]
[mm²]
[mm²]
[mm²]
[mm²]
CleanWave-12
12
16
29
176
2.5
6
2.5
6
CleanWave-18
18
24
43
219
4
10
4
10
CleanWave-30
30
40
72
359
10
25
10
25
CleanWave-40
40
56
101
452
16
35
16
35
CleanWave-55
55
80
144
538
25
2x 25
16
2x 25
CleanWave-90
90
128
231
616
50
2x 50
25
2x 50
CleanWave-140
140
201
361
972
95
2x 95
50
2x 95
CleanWave-180
180
264
476
1212
150
2x 150
95
2x 150
CleanWave-220
220
321
577
1565
2x 95
2x 185
95
2x 185
CleanWave-280
280
401
722
1568
2x 95
2x 240
95
2x 240
Table 4
                                                          
1
 According to European standards
2
 If common conductor for neutral and earth (PEN conductor)