The following formula can be used to determine the maximum heater rating per the definition of 
unconfined space:
BTU
/
hr
 =
(L1 + L2) Ft x (W) Ft x (H) Ft.
x 1000
BTU
/
hr
50
Consider two connecting rooms with an open area between, with the following dimensions: 
L
1
 = 15
1
/
2
 Ft., L
2
 = 12 Ft., W = 12 Ft., H = 8 Ft.
BTU
/
hr
 =
(15
1
/
2
  + 12) x (12) x (8)
x 1000 = 52800
BTU
/
hr
50
If there were a door between the two rooms the calculation would be based only on the room 
with the heater.
BTU
/
hr
 =
(15
1
/
2)
 x (12) x (8)
x 1000 = 29760
BTU
/
hr
50
GENERAL INSTALLATION INFORMATION
Figure 1 - Example of a Large Room with 1/2 Wall Divider 
Counter 
Fireplace 
If  the  area  in  which  the  heater  may  be  operated  is  smaller  than  that  defined  as  an 
unconfined space or if the building is of unusually tight construction, provide adequate 
combustion and ventilation air by one of the methods described in the National Fuel 
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3 or applicable local codes.