Whirlpool W10200920C Manual Do Utilizador

Página de 8
6
Option 1 - Horizontal System
The most common is the horizontal system, in which banks of 
dryers are all located in one room and vented through a common 
duct. See the following illustration for an example of a generic 
horizontal system.
A
     1"*
(25 mm)
A. 4" (102 mm) diameter rigid metal back draft damper
*Minimum spacing required between dryers
Option 2 - Vertical System
The vertical system is used in some apartment buildings that have 
a washer and dryer on each floor. Each dryer is exhausted into the 
same central vertical duct. See the following illustration for an 
example of a generic vertical system.
G
A
B
C
D
F
E
F
F
 
A. 0.6" (15 mm) water column maximum back pressure
B. Weighted dampers
C. Individual dryer exhaust - on each floor
D. 0.1" (2.5 mm) water column maximum vacuum
E. Main duct
F. Barometric damper (use depends on exhaust 
system design)
G. Source of outside air
Option 3 - Combination System
The combination system may be used in high-rise apartments, 
with a bank of dryers installed at several different levels. Each of 
these banks then exhausts into a central vertical vent. See the 
following illustration for an example of a combination system.
A
B
C
D
E
A. Central vertical duct - maximum of 
 
0.1" (2.5 mm) water column vacuum
B. Weighted damper (each dryer)
C. Maximum of 0.6" (15 mm) water column 
back pressure
D. Barometric damper (use depends on 
exhaust system design)
E. Outside air source