Details of I/O Signals
This section describes the details on the I/O signals from the high-speed counter module to the CPU module.
The I/O numbers (X/Y) in this section are shown on the assumption that the start I/O number of the high-speed counter 
module is set to 0.
Appendix 1.1
Input signals
(1) Module READY (X0)
• This signal turns on when the high-speed counter module is ready for counting operation after the CPU 
module is powered on or is reset.
• Pulses are not counted while this signal is off.
(2) CH Counter value large (point No.1) (X1, X8)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is larger than CH 
Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, Un\G37).
• This signal turns off when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to or smaller than 
CH Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, Un\G37).
(3) CH Counter value coincidence (point No.1) (X2, X9)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to CH 
Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, Un\G37). And then, the on status will be latched.
• This signal is turned off by CH Coincidence signal No.1 reset command (Y0, Y8).
• This signal is on immediately after the CPU module is powered on or is reset because both CH Present 
value (Un\G2, Un\G3, Un\G34, Un\G35) and CH Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, 
Un\G37) are set to "0".
(4) CH Counter value small (point No.1) (X3, XA)
• This signal turns on when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is smaller than CH 
Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, Un\G37).
• This signal turns off when CH Present value (Un\G2, Un\G3, Un\G34, Un\G35) is equal to or larger than 
CH Coincidence output point No.1 (Un\G4, Un\G5, Un\G36, Un\G37).
(5) CH External preset request detection (X4, XB)
• This signal is turned on by a preset command from an external input terminal. And then, the on status will be 
latched.
• This signal is turned off by CH External preset detection reset command (Y5, YD).