CHAPTER 8 FUNCTIONS
8
8.
4 Pr
eset
 F
u
nct
ion
8.4
Preset Function
This function overwrites the present counter value with the set value.
The set value is referred to as a preset value.
This function can be used to start counting pulses from the preset value.
The function can be performed using a program or an external control signal.
(1) Performing the preset function using a program
Perform the preset function by turning on CH Preset command (Y1, Y9).
No.
Description
1)
Write a value to CH Preset value (Un\G0, Un\G1, Un\G32, Un\G33) in 32-bit signed binary.
2)
On the rising edge (off to on) of CH Preset command (Y1, Y9), the value stored in CH Present value (Un\G2, 
Un\G3, Un\G34, Un\G35) is replaced with the value stored in CH Preset value (Un\G0, Un\G1, Un\G32, Un\G33).
The preset function is performed regardless of the on/off status of CH Count enable command (Y4, YC).
ON
OFF
ON
OFF
101
100
67
66
65
2
1
0
Counter input pulse
CH    Count enable command 
(Y4, YC)
CH    Preset command 
(Y1, Y9)
CH    Present value 
(Un\G2, Un\G3, Un\G34, Un\G35)
CH    Preset value
(Un\G0, Un\G1, Un\G32, Un\G33)
100
0
1)
2)
102 103 104 105