Справочник Пользователя для 3M 7620-T-95

Скачать
Страница из 20
78-8113-5098-8 Rev F 
3
Instructions For Tape Shielded Cable
2.0 Prepare Cable
2.1  Check to be sure cable size fits within kit range as shown in Table 1.
2.2  Prepare cable using dimensions shown in Figure 1Be Sure To allow for depTh of Terminal 
lug. If necessary to prevent tape shield from unrolling, hold down edge with a single wrap of 3M
 EMI 
Copper Foil Shielding Tape 1181.
NOTE: Provide additional 1/4" (6 mm) exposed conductor distance to account for growth during crimping of 
ALUMINUM lugs or connectors.
NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one 
layer. There should not be any remaining black areas, or particles, on the cable insulation layer.
2.3  Select a Scotch
®
 Mastic Sealing Strip 2230 from kit and remove white release liners. Using light tension, apply 
Single wrap of mastic around the cable jacket 1/4" (6 mm) from cut edge (Figure 1). Cut off excess.
Jacket Removal Length
6 3/4" (171 mm)
2" (51 mm)
Semi-Con
Tape Shield
Depth Of Terminal Lug + Growth Allowance
1" (25 mm)
Cable Jacket
1/4" (6 mm)
1
ST
 Scotch
®
 Mastic Strip 2230
Figure 1