System and Control Options
43
Liebert
®
 AC4
7.8
Setup Operation
The Liebert AC4 operation features allow you to set up a rotation 
sequence to alternate which devices are operating and which are 
placed on Standby, as well as test devices while in Standby mode and 
specify what to do when a Standby device goes into alarm as it is 
powered up. You may also specify delay times after an output changes 
state, directing the Liebert AC4 to wait before acknowledging inputs or 
turning an output on or off.
To change any operation features:
Log In and Choose Setup System
• From the Main Menu, use the arrows
↑↓
 to
 
choose System and 
Control, then press Enter ↵ (see 7.1 Login for help).
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
↑↓
 to
 
choose 
Setup System, then press Enter ↵.
Select Setup Operation
• From the Setup System Menu, shown at right, use the arrows
↑↓
 to
 
choose Setup Operation and press Enter ↵.
• Use the steps following Table 18 to access any of the Setup Operation options.
Table 18 shows the default settings for operation options: automatic sequencing, standby testing, 
failed standby, hold delay and restart.
Table 18
Default settings - operation features
Feature
Default
Other Options
AUTO SEQUENCING
OFF (Deactivated)
ON (Activated), 12h (Activated for 12-hour intervals)
STANDBY TESTING
OFF (Deactivated)
ON (Activated)
FAILED STANDBY
N (Deactivated)
Y (Activated)
HOLD DELAY
10:00 (No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
RESTART
00:06 (No delay)
Any time (in minutes and seconds) from 00:00 to 99:59
Setup System Menu
SETUP INPUTS
SETUP COMMON ALARM
SETUP ZONES
↑↓=NEXT
=SELECT
SETUP OUTPUTS
SETUP SYSTEM INFO
> SETUP OPERATION
Setup Operation Menu
> AUTO SEQUENCING OFF
STANDBY TESTING OFF
FAILED STANDBY
N
↑↓=NEXT
=SELECT
HOLD DELAY : 10:00
RESTART
: 00:06