Справочник Пользователя для Emerson 460
10
Leak Detection Kit Installation Scenarios
Scenarios
Upflow
Unit
Detection
around
entire unit
Upflow
Unit
Detection
on sides and
in front of unit
Downflow
Unit
Detection
around
entire unit
Downflow
Unit
Detection
on sides and
in front of unit
Distance from unit
Distance:
In back
On sides
In front
2 ft
2 ft
2 ft
2 ft
2 ft
No cable behind
2 ft
2 ft
2 ft
1 ft
1 ft
6 ft
1 ft
6 ft
No cable behind
1 ft
6 ft
6 ft
Unit
(footprint-in.)
Part number
Challenger
(32.5 x 32.5)
LT460-Z30
LT460-Z20
LT460-Z30
LT460-Z25
Himod
(69 x 35)
LT460-Z35
LT460-Z20
LT460-Z35
LT460-Z25
Deluxe System/3
(50 x 35)
LT460-Z30
LT460-Z20
LT460-Z35
LT460-Z25
(74 x 35)
LT460-Z35
LT460-Z20
LT460-Z35
LT460-Z25
(99 x 35)
LT460-Z45
LT460-Z25
LT460-Z45
LT460-Z30
(122 x 35)
LT460-Z45
LT460-Z25
LT460-Z45
LT460-Z30
DS
(73 x 35)
LT460-Z35
LT460-Z20
LT460-Z45
LT460-Z30
(86 x 35)
LT460-Z35
LT460-Z20
LT460-Z45
LT460-Z30
(98 x 35)
LT460-Z45
LT460-Z25
LT460-Z45
LT460-Z30
(109 x 35)
LT460-Z45
LT460-Z25
LT460-Z45
LT460-Z30
(132 x 35)
LT460-Z45
LT460-Z25
LT460-Z45
LT460-Z30
2-ft clearance
in front
2-ft clearance
in front
6-ft clearance
in front
6-ft clearance
in front