GAS CONNECTION
STEP 1.
Make the gas connection between the manual shut off valve and regulator located inside
heater cabinet.  Hold regulator when tightening connection to prevent damage to regulator
and internal tubing.  See Figure 6 for completed installation.
NOTE:
All piping and connection must be checked for leaks by the installer.  If connections are not
exposed, a pressure test must be run.  The appliance and its individual shut off valve must
be disconnected from the gas supply piping system during any pressure testing at pressures
in excess of ½ psig (3.5 kPa).  The appliance must be isolated from the gas supply piping
system by closing its individual manual shut off valve during any pressure testing of the gas
supply piping system at test pressures equal to or less than ½ psig (3.5kPa).
Internal Regulator
             (Supplied)
Union
Drip Leg
Manual Shut Off
Outside Reg.
Supplied
by Gas Co.
1/8” NPT Plug
FIGURE 6
Manual
Cut off
Valve
1/8” NPT
Pressure
Plug
Drip
Leg
GAS PIPING WITH VF-FSK KIT
FIGURE 6A
Page 10
BURNER ORIFICE
This appliance is orificed at the factory for elevations up to 2,000 ft.  If installed above 2,000 ft. the BTU
input must be reduced 4% per 1,000 ft.  See the following orifice chart for the proper orifice for a specific
elevation.
                                                                    SPECIFIC ELEVATION
  Model No.
0 to
2,000 -
4,000 -
6,000 -
8,000 -
  No.
2,000’
4,000’
6,000’
8,000’
10,000’
                                                                           NATURAL GAS
  BFT101
1.55 mm
54
54
55
55
  BFT201
43
44
45
47
48
  BFT301
36
38
40
41
43
                                                                                     L.P. GAS
  BFT102
63
65
65
66
68
  BFT202
55
55
56
56
57
  BFT302
52
53
53
54
54