Справочник Пользователя для SPX Cooling Technologies 98-1514E

Скачать
Страница из 32
25
Seasonal Shutdown instructions
When the system is to be shut down for an extended period of time, it is 
recommended that the entire system (cooling tower, system piping, heat 
exchangers, etc.) be drained. Leave the basin drains open.
During shutdown, clean the tower (see Warning, page 20) and make any 
necessary repairs. Pay particular attention to mechanical equipment.
Following each year’s shutdown and cleaning, inspect the tower’s metal 
surfaces for evidence of the need to apply a protective coating. Do not 
misinterpret grime—and transient rust from the piping system—as a need 
to have the tower painted. If relatively bright metal can be exposed by 
cleaning, consider that the galvanizing has remained effective. Unless there 
is evidence of a generalized failure of the galvanizing, localized touch-up 
should be all that is required.
To the extent that the galvanizing (zinc coating) still exists, paint will
not adhere to it readily. Contact the manufacturer of the coating you 
intend to use for instructions.
Tower framework: Check structural bolted connections and tighten as 
required.
Fans: Check fan assembly bolting and tighten as required. Use torque 
settings prescribed in the fan manual.
Fiberglass Components: Check all fiberglass parts for exposed glass 
fibers. If found, the affected surfaces should be recoated using a two-
part polyamide epoxy primer to promote adhesion and a two-part acrylic 
polyurethane enamel for the topcoat.
Fan shaft bearings: Lubricate fan shaft bearings at close of each operat-
ing season—see page 24. 
Electric motors: Clean and lubricate motor at close of each operating 
season (refer to motor manufacturer’s recommendations.) Check motor 
anchor bolts and tighten as required. 
Do not start motor before determining that there will be no interfer-
ence with free rotation of the fan drive.
The motor should be operated for three hours at least once a month. This 
serves  to  dry  out  windings  and  re-lubricate  bearing  surfaces—refer  to 
Marley Electric Motor User Manual 92-1475.
At  start  of  new  operating  season,  make  sure  bearings  are  adequately 
Maintenance