Blowdown,  or  bleed-off  is  the  continuous  removal  of  a  portion  of  the 
water from the circulating system. It is used to prevent  dissolved solids 
from concentrating to the point where they will form scale. The amount 
of blowdown required depends upon the cooling range (design hot water 
temperature minus design cold water temperature) and the composition 
of  the  make-up  water  (water  added  to  the  system  to  compensate  for 
losses by blowdown, evaporation, and drift). The following table shows 
the amount of blowdown (percent of total water flow) required to maintain 
different concentrations with various cooling ranges:
Example: 150,000 gpm (9465 L/s) circulating rate, 28°F (15.56°C) cooling 
range. To maintain 3 concentrations, the required blowdown is 1.1% or 
.011 times 150,000 gpm (9465 L/s) which is 1650 gpm (104.1L/s). 
If tower is operated at 3 concentrations, circulating water will contain three 
times as much dissolved solid as the make-up water, assuming none of 
the solids form scale or are otherwise removed from the system.
The use of corrosion and scale inhibitors is strongly recommended.
Chemical Treatment
In some cases chemical treatment of the circulating water is not required 
if adequate blowdown is maintained. In most cases, however, chemical 
treatment is required to prevent scale formation and corrosion. Sulfuric acid 
or one of the polyphosphates is most generally used to control calcium 
carbonate scale. Various proprietary materials containing phosphates or 
other compounds are available for corrosion control. When water treatment 
chemicals are required, the services of reliable water treating companies 
should be obtained.
The  circulating  water  pH  should  be  maintained  between  .0  and 
..
The Langelier index (calcium carbonate saturation index) has proven to be 
an effective tool in predicting the aggressiveness of cooling tower water 
toward concrete. The Langelier index relates the methyl orange alkalinity, 
the calcium hardness, the total solids, the pH value, and the temperature 
of the water. From these values it is possible to calculate the index and 
Number of Concentrations
Cooling Range
1.5X
2.0X
2.5X
3.0X
4.0X
5.0X
6.0X
10°F (  5.56°C)
1.58
0.78
0.51
0.38
0.25
0.18
0.14
15°F (  8.33°C)
2.38
1.18
0.78
0.58
0.38
0.28
0.22
20°F (11.11°C)
3.18
1.58
1.05
0.78
0.51
0.38
0.30
25°F (13.89°C)
3.98
1.98
1.32
0.98
0.64
0.48
0.38
30°F (16.67°C)
4.78
2.38
1.58
1.18
0.78
0.58
0.46
Multipliers are based on drift of 0.02% of the circulating water rate.
Water Treatment
 
 Note
 
 Note