WHEN COMMUNICATING DATA USING THE MC PROTOCOL
9
9 - 15
9.2 List of Commands and Functions for The MC protocol
The following table lists the commands and functions when an external device 
accesses the PLC.
*1
When the double word data is read using the user program, etc., read out the 32bit data at once.
Function
-
Command/response type
Processing
Number of points
processed per
communication
Device 
 
memory 
Batch read
Bit units
00
H
Reads bit devices (X, Y, M, S, T, C) in 1-point units.
256 points
Word units
01
H
Reads bit devices (X, Y, M, S, T, C ) in 16-point units.
32 words (512 points)
Reads word devices (D, R, T, C ) in 1-point units. (*1)
64 points
Batch write 
Bit units
02
H
Writes to bit devices (X, Y, M, S, T, C ) in 1-point units.
160 points
Word units
03
H
Writes to bit devices (X, Y, M, S, T, C ) in 16-point units.
10 words (160 points)
Writes to word devices (D, R, T, C ) in 1-point units.
64 points
Test
(Random write) 
Bit units
04
H
Sets/resets bit devices (X, Y, M, S, T, C) in 1-point units 
by arbitrarily designating the devices and device number.
80 points
Word units
05
H
Sets/resets bit devices (X, Y, M, S, T, C) in 16-point units 
by arbitrarily designating the devices and device number.
10 words (160 points)
Sets/resets word devices (D, R, T, C) in 1-point units by 
arbitrarily designating the devices and device numbers.
Not applicable for 32 bit devices from C200 to C255.
10 points
PLC control
Remote RUN
13
H
Requests the remote RUN/STOP to PLC.
Remote STOP
14
H
PLC model name read
15
H
Reads PLC model name code.
Loop test
16
H
Returns the character received from the other node to 
that node with the data as it is.
254 bytes