9 - 33
MELSEC-F
WHEN COMMUNICATING DATA USING THE MC PROTOCOL
9
9 - 33
9.3.7 Test in word units (random write) (command: 05)
The examples shown in this section explain the command/response format when 
writing data by designating word device memories and bit device memories (16 point 
units) arbitrarily. These examples are not applicable for writing the current values of 
C200 to C255 (32-bit devices).
For more details on the order and contents of data items of the areas marked by " " 
shown in the control procedure diagram, see Subsection 9.1.2.
[Control procedure]
Specifying Y20 to Y37 to on/off, R26 to "1234
H
," and the current value of C18 to "50
H
at the PLC on which the Ethernet module is loaded.
(1) Communication in binary code
Current value of CN18
50
H
1234
H
Y30
Y37
Y20
Y27
0
0
1
0
1
0
0
1
0
1
1
1
1
0
1
1
Y20
R26
1....ON
0....OFF
05
H
FF
H
0A
H
03
H
00
H
80
H
00
H
00
H
00
H
20
H
59
H
29
H
7B
H
1A
H
00
H
00
H
00
H
20
H
52
H
34
H
12
H
12
H
00
H
00
H
00
H
4E
H
43
H
50
H
00
H
00
H
85
H
00
H
L
L
-
H
L
H
-
-
-
H
L
-
H
L
-
-
-
H
L
-
H
L
-
-
-
H
(Data name)
External device
side
(Example)
(Data name)
PLC side
(Example)
Subheader
PC No.
Number of device points
Monitoring
timer
Designated device
Subheader
Complete code
to
to
Designated device
Designated device
Device data
(ON/OFF designation)
Device data
Device data