Справочник Пользователя для Mitsubishi Electronics fx3u

Скачать
Страница из 284
11 - 2
TROUBLESHOOTING
11
11 - 2
11
MELSEC-F
11.1 How to Check Errors Using LED Displays
This section describes the errors that can be checked with the LED displays on the 
front of the Ethernet module.
11.1.1 Checking error display
The following can be checked with the LED displays on the front of the Ethernet 
module.
<Ethernet module LED>
(Continues on the following page)
LED name
Status to check
Cause/corrective action
1
RUN
Turns off after powering on 
the Ethernet module. 
1) Watchdog timer error
• A watchdog timer (approximately 600 ms) error is detected by the self diagnosis 
function of the Ethernet module.
2) Base module power is OFF, or the extension cable is not connected.
2
INIT.
Off
1) Failed to re-initialization due to a parameter error
• Check/correct the parameter setting values for the Ethernet modules using a sequence 
program or the FX Configurator-EN-L and re-download.
2) Base module power is OFF, or the extension cable is not connected.
3
100M
Does not turn on
1) Using 10Mbps HUB
• Initial processing.
• Replace with 100Mbps HUB.
2) Does not turn on using 100Mbps HUB
• Check the connection of the connectors on the Ethernet side and the HUB side.
• Replace the cable.
4
ERR.
Turns on after powering on 
the Ethernet module.
1) Module parameter setting error
• Check/correct the parameter setting values for the Ethernet modules using the 
sequence program or the FX Configurator-EN-L and re-download.
2) PLC error
• When the PLC  [RUN] LED is off/flashing, or the [ERR.] LED is on, check the content of 
the error occurring in the PLC and correct the problem.
3) Ethernet module error (H/W error)
4) Base module power is OFF, or the extension cable is not connected.
5
COM.ERR.
Turns on after powering on 
the Ethernet module.
Or turns on temporarily
1) Check the contents of the error using the error codes stored by the error detection of the 
following processing and remove the causes.
• Initial processing
• Fixed buffer send processing
• E-mail send processing
• Open processing
• MC protocol communication processing
• Other processing (processing for which error codes are stored in the error log area)
2) For a list of error codes, see Section 11.4.