11 - 9
MELSEC-F
TROUBLESHOOTING
11
11 - 9
11.2.2 Ethernet diagnostics
[Purpose]
The block status of an Ethernet module, parameter settings, communication status, 
error log and others can be checked using the Ethernet diagnostic function of 
 
FX Configurator-EN-L.
[Operating procedure]
FX Configurator-EN-L   
   
[Ethernet diagnostics screen]
[Explanation of items]
No.
Item
Description
Setting range
1
Change IP address display
Switches the IP address display between decimal and hexadecimal. 
Decimal/hexadecimal
2
Selection from the various 
information monitors
Various types of information for the Ethernet module can be monitored. 
(See Subsection 11.2.1 for the buffer memory corresponding to the display contents.)
3
Performs the PING test on the external device. (See Subsection 5.4.1, Subsection 
5.4.2.)
4
Clicking this button turns the [COM.ERR.] LED off. (See Subsection 11.1.2.)
5
Clicking this button executes the Ethernet diagnostics.
The display is updated during monitoring.
6
Clicking this button stops the Ethernet diagnostics.
The display is retained while monitoring is stopped.
7
Clicking this button executes the clears the log.
Diagnostics
Diagnostics
7)
3)
4)
5)
6)
1)
2)
PING test
COM. ERR off
Start monitor
Stop monitor
Clear history