Справочник Пользователя для Mitsubishi Electronics fx3u

Скачать
Страница из 284
11 - 18
MELSEC-F
TROUBLESHOOTING
11
11 - 18
11.4.3 Abnormal codes returned during communication using MC protocol
This section explains the abnormal codes (error codes) that are added to responses 
when communicating using MC protocol (An abnormal code is added only when an 
end code is "5B".)
For more details on the end codes (error codes) that are added to responses, see 
Subsection 11.4.2.
For more details on the end codes (error codes) that are stored in the buffer memory 
of the Ethernet module, see Subsection 11.4.4.
Error code
(hexadecimal)
Error
Description of error
Corrective action
10
H
PC number error
The PC number designated was not "FF".
(1)Set the PC number to "FF"..
11
H
Mode error
Poor communication between the Ethernet module and the PLC 
(1)After the Ethernet module receives a request successfully from an 
external device, the Ethernet module and the PLC could not 
communicate for some reason (noise, etc.).
(1)Communicate again. If an error occurs again, 
check noise, etc. and replace the Ethernet 
module, then communicate again.
18
H
Remote error
Remote RUN/STOP not accessible.
 
The PLC base module status is CPU ERR or PROG ERR.
(1)Check whether or not the base module has a 
CPU ERR (light on) or PROG ERR (flashing 
light).
00
H
Abnormal code
Response format
Subheader
End code
When an abnormal code is stored, the end code is "5B
H
."