IDV380/IDV490 Fireplace Insert
iNSeRt iNStAllAtiON 
Only  persons  licensed  to  work  with  gas 
piping may make the necessary gas con-
nections to this appliance.
A manual shut-off valve is factory installed 
upstream of the appliance. union tee and 
plugged 1/8"  NPt pressure  tapping point 
should be installed upstream of the appli-
ance. 
Figure 15
A listed manual shutoff is factory installed upstream of appliance. Union tee and plugged 1/8" 
NPT pressure tapping point should be installed upstream of the appliance. Figure 15.
iMPORtANt: The main gas valve is for turning on or shutting off the gas to the insert. 
Check your building codes for any special requirements for 
locating equipment shutoff valve to inserts.
Apply pipe joint sealant lightly to threads. This will prevent 
excess sealant from going into pipe. Excess sealant in pipe 
could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in 
supply line as shown in Figure 15. Locate sediment trap/drip 
leg where it is within reach for cleaning. Install in piping system between fuel supply and burner 
system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment 
trap traps moisture and contaminants. This keeps them from going into the burner system 
gas controls. If sediment trap/drip leg is not installed or is installed wrong, burner system may 
not run properly. 
NOTE : The gas line connection may be made using 1/2" rigid tubing or an approved 
flex connector. Since some municipalities have additional local codes it is always best 
to consult your local authorities and the current edition of the National Fuel Gas Code 
ANSI.Z223.1, NFPA54. In Canada CSA-B149 (1 or 2) Installation Code. 
3" Minimum
FP1931
gas connection
9/08
Approved Flexible 
Gas Line Supplied 
with Appliance
Tee Joint
Pipe Nipple
Cap
Natural Gas
From Gas Meter
(4.5" w.c. to 10.5" w.c. Pressure)
Propane/lP
From External Regulator
(11" w.c. to 13" w.c. Pressure)
Figure 15 -
Gas Connection
W
ARN
iNG
CA
uti
ON
use  pipe  joint  sealant  that  is  resistant  to 
liquid petroleum (lP) gas.
CA
uti
ON