HDV Series Direct Vent Gas Fireplace
8
56D3048
Note : The gas line connection may be made using 1/" rigid tubing or an approved flex connector. 
Since some municipalities have additional local codes it is always best to consult your local authorities 
and the current edition of the National Fuel Gas Code ANSI.Z3.1, NFPA54. In Canada CSA-B149 
(1 or ) Installation Code. 
A listed manual shutoff valve must be installed upstream of 
the  appliance.  Union  tee  and  plugged  1/8"  NPT  pressure 
tapping point should be installed upstream of the appliance. 
Figure 42
IMPoRtANt: Install main gas valve (equipment shutoff valve) 
in an accessible location. The main gas valve is for turning on 
or shutting off the gas to the fireplace. 
Check  your  building  codes  for  any  special  requirements  for  locating  equipment  shutoff  valve  to 
fireplaces.
Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going 
into pipe. Excess sealant in pipe could result in clogged burner system valves.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 42. Locate 
sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel 
supply and burner system. Locate sediment trap/drip leg where trapped matter is not likely to freeze. 
A sediment trap traps moisture and contaminants. This keeps them from going into the burner system 
gas con
trols. If sediment trap/drip leg is not installed or is installed wrong, burner system 
may not run properly. 
W
ARNING
only  persons  licensed  to  work  with  gas 
piping  may  make  the  necessary  gas 
connections to this appliance. 
CA
ut
Io
N
A manual shutoff valve must be installed 
upstream  of  the  appliance.  union  tee 
and  plugged  1/8"  NPt  pressure  tapping 
point should be installed upstream of the 
appliance. See Figure 38.
CA
ut
Io
N
use pipe joint sealant that is resistant to 
liquid petroleum (lP) gas.
3" Minimum
FP1978
gas connection
Pipe Nipple
Cap
Figure 42 - 
Gas Connection 
Tee Joint
Approved Flexible 
Gas Line 
CSA Design-Certified Equipment Shutoff Valve 
with 1/8" NPT Tap*
Sediment Trap/Drip Leg 
Natural Gas
From Gas Meter 
(4.0" w.c. to 10.5" w.c. Pressure)
Propane/lP
From External Regulator 
(11" w.c. to 13" w.c. Pressure)
FIRePlACe INStAllAtIoN