12. Test run
12.1. The following phenomena do not represent faults.
Phenomenon
Display of remote controller
Cause
Indoor unit does not perform cooling 
(heating) operation. 
“Cooling (heating)” flashes
When another indoor unit is performing the heating (cooling) operation, the 
cooling (heating) operation is not performed.
The auto vane rotates and begins to blow air 
horizontally.
Normal display
If air has been blowing downward for 1 hour during cooling, the unit may 
automatically change to horizontal blowing with the control operation of the 
auto vane. During defrosting or immediately after heating start-up/shut-down, 
the auto vane automatically rotates to blow air horizontally for a short period 
of time.
Fan setting changes during heating.
Normal display
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature 
at thermostat ON.
Fan stops during heating operation.
Defrost display
The fan is to stop during defrosting.
Fan does not stop while operation has been 
stopped.
No lighting
The fan is set to run for 1 minute after stopping to exhaust residual heat (only in 
heating).
No setting of fan while start SW has been 
turned on.
Heat ready
Ultra low-speed operation for 5 minutes after SW ON or until piping 
temperature becomes 35°C, low speed operation for 2 minutes thereafter, and 
then set notch is commenced (Hot adjust control). 
Indoor unit remote controller shows “H0” 
or “PLEASE WAIT” indicator for about five 
minutes when turning ON universal power 
supply.
“H0” or “PLEASE WAIT” flashes
The system is being started up.
Operate remote controller again after “H0” or “PLEASE WAIT” disappear.
Drain pump does not stop when unit is 
stopped.
Light out
After cooling operation stops, the unit continues to operate drain pump for 
three minutes and then stops it.
Drain pump continues to operate while unit 
has been stopped.
Unit continues to operate drain pump if drainage is generated, even during a 
stop.
Indoor unit emits noise when switching from 
heating to cooling and vice versa.
Normal display
This is a switching sound of the refrigerant circuit and does not imply a 
problem.
Immediately after startup, the indoor unit 
emits the sound of the refrigerant flow.
Normal display
Unstable flow of the refrigerant emits a sound. This is temporary and does not 
imply a problem.
Warm air comes from an indoor unit that is 
not performing a heating operation.
Normal display
The LEV is slightly open to prevent refrigerant, of the indoor unit that is not 
performing the heating operation, from being liquefied. This does not imply a 
problem.
13. Information on rating plate
Model
P200YJM-A
P250YJM-A
P300YJM-A
P350YJM-A
P400YJM-A
P450YJM-A
Unit combination
-
-
-
-
-
-
Refrigerant (R410A)
6.5kg
8.0kg
8.0kg
11.5kg
11.5kg
11.8kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
190kg
200kg
215kg
250kg
250kg
290kg
Model
P500YSJM-A
P500YSJM-A1
P550YSJM-A
Unit combination
P250
P250
P300
P200
P300
P250
Refrigerant (R410A)
8.0kg
8.0kg
8.0kg
6.5kg
8.0kg
8.0kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
200kg
200kg
215kg
190kg
215kg
200kg
Model
P600YSJM-A
P600YSJM-A1
P650YSJM-A
Unit combination
P350
P250
P300
P300
P350
P300
Refrigerant (R410A)
11.5kg
8.0kg
8.0kg
8.0kg
11.5kg
8.0kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
250kg
200kg
215kg
215kg
250kg
215kg
Model
P700YSJM-A
P700YSJM-A1
P750YSJM-A
Unit combination
P350
P350
P400
P300
P400
P350
Refrigerant (R410A)
11.5kg
11.5kg
11.5kg
8.0kg
11.5kg
11.5kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
250kg
250kg
250kg
215kg
250kg
250kg
Model
P800YSJM-A
P800YSJM-A1
P850YSJM-A
P900YSJM-A
Unit combination
P450
P350
P400
P400
P450
P400
P450
P450
Refrigerant (R410A)
11.8kg
11.5kg
11.5kg
11.5kg
11.8kg
11.5kg
11.8kg
11.8kg
Allowable pressure (Ps)
HP: 4.15 MPa, LP: 2.21 MPa
Net weight
290 kg
250 kg
250kg
250kg
290kg
250kg
290kg
290kg
Model
P950YSJM-A
P1000YSJM-A
Unit combination
P400
P300
P250
P400
P300
P300
Refrigerant (R410A)
11.5kg
8.0kg
8.0kg
11.5kg
8.0kg
8.0kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
250kg
215kg
200kg
250kg
215kg
215kg
Model
P1050YSJM-A
P1100YSJM-A
Unit combination
P400
P350
P300
P400
P350
P350
Refrigerant (R410A)
11.5kg
11.5kg
8.0kg
11.5kg
11.5kg
11.5kg
Allowable pressure (Ps)
HP: 4.15MPa, LP: 2.21MPa
Net weight
250kg
250kg
215kg
250kg
250kg
250kg
WT05962X01_GB.indd   22