Service Manual  17
Piping Length And Elevation
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Oil trap should be installed every 5~7meters (16.4~23.0ft).
In case more than 5m(16.4ft)
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
Pipe Size
Capacity
(Btu/h)
Suction
Evap
Max. 
length
m(ft)
Additional Refrigerant
g/m(oz/ft)
Max.
Elevation
B
m(ft)
Standard
Length
m(ft)
9k
3/8"
1/4"
7.5(25)
7.5(25)
15(49)
20(0.22)
1/2"
1/4"
7.5(25)
7.5(25)
15(49)
20(0.22)
12k
1/2"
1/4"
7.5(25)
7.5(25)
15(49)
20(0.22)
18k
1/2"
1/4"
7.5(25)
15(49)
30(98)
20(0.22)
5/8"
1/4"
7.5(25)
7.5(25)
15(49)
20(0.22)
24k
5/8"
1/4"
7.5(25)
7.5(25)
15(49)
20(0.22)
Installation