Operation 
Function of Controls
Operation 
• DISPLAY
1) C/O Model 
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compres-
sor off.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
■ Cooling Mode Operation
• When the intake air temperature reaches 0.5°C(0.9°F) below the setting temp, the compressor and
the outdoor fan stop.
• When it reaches 0.5°C(0.9°F) above the setting temp, they start to operate again.
Compressor ON Temp 
➲ Setting Temp+0.5°C(0.9°F)
Compressor OFF Temp
➲ Setting Temp-0.5°C(0.9°F)
• While in compressor running, operating with the airflow speed set by the remote control. While in
compressor not running, operating with the low airflow speed regardless of the setting.
■ Healthy Dehumidification Mode
• When the dehumidification operation input by the remote control is received, the intake air tempera-
ture is detected and the setting temp is automatically set according to the intake air temperature.
26°C(78.8°F) 
≤ Intake Air Temp     
➲  25°C(77°F)
24°C(75.2°F) 
≤ Intake Air Temp<26°C(78.8°F) ➲  Intake Air Temp-1°C(1.8°F)
18°C(64.4°F) 
≤ Intake Air Temp<24°C(75.2°F) ➲  Intake Air Temp-0.5°C(0.9°F)
Intake Air Temp<18°C(64.4°F)
➲  18°C(64.4°F)
34 Room Air Conditioner